AP&T
Information Request
1. Skagway ore terminal KW draw ? _300-900 kW_______
2. White Pass Shops KW draw? ____300-500 kW______
3. Underwater cable KW limit?_____>20,000 kW______
4. Present diesel KW average supplement?__250-800 kW__ (Haines )
5. Diesel KW max output?_____>5,500 kW max 3465 kW firm_______ (Haines )
6. Estimated cruise ship KW draw?__7,000 – 12,000 kW at dock per ship___
current system: 5,000 kW peak load; Current Haines peak load: 2700 kW
Using the Integrated Resource Plan from the AEA, for Haines and Skagway combined:
7. Estimated Haines KW need in 10 years?
_5,200 kW – 7,000 kW likely at the reference point of 6,400 kW According to the SEIRP: Mining peripherals would push loads above the reference load toward the high end forecast, but the local forecast does not include enough specifically for a mine. Separately, the High forecast would not cover the load requirements for cruise ship interconnection and sales.
8. Estimated Haines KW need in 20 years?
___5,500 kW- 8,100 kW likely near the reference point of 6,800 kW See above